This paper investigates the performance of a 960 kWP photovoltaic (PV) system, located in southern Italy. Monitoring data over a 43 months period are used to evaluate the monthly average of energy yields, losses and efficiency. The performance ratio and the capacity factor were 84.4% and 15.6%, respectively. The yearly average module efficiency was 15.3% and the system efficiency was 14.9%, whereas the capture and system losses were 0.6 h/day and 0.1 h/day respectively. The degradation rate of the PV system, after continuous outdoor exposure, has been estimated at about 1.48%/year by applying the Classical Seasonal Decomposition (CSD) method. A comparison in terms of degradation rate is made with other PV plants installed in different climates to address the need of standard methods to determine this crucial parameter. The actual performance of the studied PV system is compared with the expected outcomes by using two widely used PV simulation tools, SAM and PVsyst. A detailed difference analysis is carried out to evaluate the accuracy of the SAM and PVsyst models. Results show that the yearly average energy injected into the grid was under-estimated by 3.0% by SAM and by 3.3% by PVsyst, but overall PVsyst outperforms the SAM tool. Results provide reliable data on the plant and demonstrate its good performance compared to other plants located in the same climate. The results can be used to improve the prediction of the performance of future PV of systems in the Mediterranean climate, and also provide a useful dataset for comparative studies

Long term performance, losses and efficiency analysis of a 960 kWp photovoltaic system in the Mediterranean climate

Malvoni, M.
Writing – Original Draft Preparation
;
Maggiotto, G.
Investigation
;
Congedo, P. M.
Writing – Review & Editing
;
De Giorgi, M. G.
Supervision
2017-01-01

Abstract

This paper investigates the performance of a 960 kWP photovoltaic (PV) system, located in southern Italy. Monitoring data over a 43 months period are used to evaluate the monthly average of energy yields, losses and efficiency. The performance ratio and the capacity factor were 84.4% and 15.6%, respectively. The yearly average module efficiency was 15.3% and the system efficiency was 14.9%, whereas the capture and system losses were 0.6 h/day and 0.1 h/day respectively. The degradation rate of the PV system, after continuous outdoor exposure, has been estimated at about 1.48%/year by applying the Classical Seasonal Decomposition (CSD) method. A comparison in terms of degradation rate is made with other PV plants installed in different climates to address the need of standard methods to determine this crucial parameter. The actual performance of the studied PV system is compared with the expected outcomes by using two widely used PV simulation tools, SAM and PVsyst. A detailed difference analysis is carried out to evaluate the accuracy of the SAM and PVsyst models. Results show that the yearly average energy injected into the grid was under-estimated by 3.0% by SAM and by 3.3% by PVsyst, but overall PVsyst outperforms the SAM tool. Results provide reliable data on the plant and demonstrate its good performance compared to other plants located in the same climate. The results can be used to improve the prediction of the performance of future PV of systems in the Mediterranean climate, and also provide a useful dataset for comparative studies
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11587/418342
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 130
  • ???jsp.display-item.citation.isi??? 109
social impact